Title
-
EWP 9-3-2 Douglas Elementary Equipment Receipts 1958 15
-
Tag
-
inspection, boilers, water heaters, maintenance, safety, repair, adjustment, standards, historical
-
Place
-
Virginia, US
-
Identifier
-
1028454
-
Is Version Of
-
1028454_EWP_9-3-2_Douglas_Elementary_Equipment_Receipts_1958_15.pdf
-
Is Part Of
-
Deeds Schools and Construction
-
Date Created
-
2023-08-02
-
Format
-
.pdf
-
Number
-
39a197943013aa92207d097b8a97fad89de9a4a64d6bc47a05a23f5c556b8e64
-
Source
-
/Volumes/T7 Shield/EWP/Elements/EWP_Files/source/Ingest One/9 Deeds Schools and Construction/9-3 Construction Sales and Strategy/9-3-2 Colored Construction Files/9-3-2 Douglass Elementary/EWP_9-3-2_Douglas_Elementary_Equipment_Receipts_1958_15.pdf
-
Publisher
-
Digitized by: Edwin Washington Project
-
Rights
-
Loudoun County Public Schools
-
Language
-
English
-
Replaces
-
/Volumes/T7 Shield/EWP/Elements/EWP_Files/source/Ingest One/9 Deeds Schools and Construction/9-3 Construction Sales and Strategy/9-3-2 Colored Construction Files/9-3-2 Douglass Elementary/EWP_9-3-2_Douglas_Elementary_Equipment_Receipts_1958_15.pdf
-
extracted text
-
THE
FORD ST E,dM BOI L E R
TNSPECTION AND INSURANCE COMPANY
H,A,.RT
HARTFORD
W. R, SULLIVAN
CONNECTICUT
EIALTIMORE
MANAGER
H, E. BELCHER
OFFICE
2225 NORTH CHARLE6 STREET
BALTIMORE
IA. MARYTAND
CHIEF INSPECTOR
Itioveuber 1!, 1958
REPORT OF INSPECTION
John E'S. $torFs
South Side of
INS eecron
DATE OF INSPECTIO
D
LOCATION
Caet fron
tocated
Boiler No. I. H.B. F1ills
- Boiler Roon
ln service.
Thg exposed nechanisms of the conbined lor water fuel supply cut-off
and water leve1 control has been sprayed with paint. The-ebntrol ehould
be diseantled and all traces of palnt renoved. whlch ean affeet the
proper operation of this eontrol.
It is reconmended that the personnel la charge of this boller be
thoroughly tnstructed and the varioue eontrols tested at frequent
intervals ts iasure that t hey are ln proper operating condition and if
Inopected externally while
defecte are found, repatrs should be nade pronptly.
Air Tank No. NB-liiiB-PST-88136t1, Lrz'' x 2tLOB
toaated - Botler Rooa
Inspected externally wtrlJ.e in serviee.
Although this tank is nounbed oa vibratlon elininatore, it ls not
properly seeured to the floor. the tank should be proirerly aounted so
that vibration will not eause novenent rhich rrill reflect on the piping
and wtring.
draln, on the under-side of the tank, is plrrgged. A new drain coek
should be lnstalled so that aecumulated, dondensate and oL1 aay be
drained off at weekly intervals.
The
Electric Water Heater No. l, 8r x 2t3;
Located, - Kitehen
Inspected externelly while in servleer
?he safet'y rellef valve lnstalled on this obJect is leaklng. ft
_l
I--ro
County $chool Board
Leesburg, Virginia
LI
FENM NO.3FI
of Loudoun County
should
THE HARTFoRD STEAM EIoILER INSPEGTIoN ANrr INSURANCE CoMPANY
PAGE.....?.......
REFORT OF INSPECTION
County $ehool Board
of
Loudoun County
November
19,
1958
be overhaul-ed and plaeed in proper operating condition or replaced as
is found neeessary. This valve should be set to relieve at not more
than 85 psi.
$torage l$ater Heater No. I{B-H$B-2085, 2t
'
- Boiler Rooa
fnspected externally whlle ln servLce.
Electric Water Heater No. t8G-9O89
Located.
x
5t6$
toeated - Bol1er Hoon
fnspected externaLly while ftlLed and idle.
relief valves, installed on these obJeets, for overpressure proteetlonp etr€ not equipped witb test levers. For more adequate protectlon, it is suggested that the present valves be replaced with
ASMS approved National Board rated safety reltef vaLves, set to relLeve
at not more thaa L25 psi.
Ihe
fhe temperature eontrol on the storage water heater has been partially
painted and lt is recommended that these paint deposits be rennoved from
the operating nechanierss to prevent failure.
,lhe above conditions were all discussed wlth !4r. Durffey, Illechanical
Supervisor, at the tine of inspection and tt is understood that prounpt
comective action w111 be taken.
Yours very
JIiH:AMO
Form No. l8E
truly,
€ Inspector.
EnZ' ""/.;",u1